Follow
J041--Condensing Unit Repair
Active
Contract Opportunity
Notice ID
36C24123Q0198
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
241-NETWORK CONTRACT OFFICE 01 (36C241)
Looking for contract opportunity help?

Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.

General Information
  • Contract Opportunity Type: Sources Sought (Original)
  • All Dates/Times are: (UTC-05:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Original Published Date: Dec 22, 2022 09:08 am EST
  • Original Response Date: Dec 29, 2022 12:00 pm EST
  • Inactive Policy: Manual
  • Original Inactive Date: Feb 27, 2023
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: J041 - MAINT/REPAIR/REBUILD OF EQUIPMENT- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
  • NAICS Code:
    • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
  • Place of Performance:
    West Haven VAMC West Haven , CT 06516
Description

West Haven VAMC
950 Campbell Avenue
West Haven, CT 06516

Scope of Work
BLDG. 15-Condensing unit repair

Work covered under this agreement includes the following items.
Secure air-cooled condensing unit and disconnect electrical power and controls. Apply
appropriate lock out tag out devices (LOTO) and tags to secure energy sources.
Circuit A leak Check & Repair Currently out of refrigerant
Pressurize circuit with nitrogen and check for leaks.
Repair leak.
Replace sight glass and filter drier.
Pressure test circuit for leaks.
Evacuate circuit and re-charge with new R-22 refrigerant (allowance of 90 lbs. of R22
shall be included).
Circuit B repairs Compressor and condenser fan motor are seized
Reclaim refrigerant charge and store for re-use.
Disconnect and remove failed compressor.
Furnish and install new compressor.
Disconnect and remove failed condenser fan motor.
Furnish and install new motor and fan blade.
Replace sight glass and filter drier with new
Replace crank case heater with new.
Pressure test circuit for leaks.
Evacuate and re-charge with re-claimed refrigerant.
Remove LOTO & Reconnect existing electrical power and controls circuitry. Start-up unit and
check operation.

Equipment Schedule:
Equipment Quantity Manufacturer Model/Serial #
Air cooled condensing unit 1 Trane TTA180B300CC /
M273TT4AH
Attachments/Links
Contact Information
Contracting Office Address
  • ONE VA CENTER
  • TOGUS , ME 04330
  • USA
Primary Point of Contact
Secondary Point of Contact


History
  • Dec 22, 2022 09:08 am ESTSources Sought (Original)

TRY FOR FREE

Not a USAOPPS Member Yet?

Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.

Start Free Trial Today >